Why doesn't Iref_sd = 0 when 0 is input to Tref and ωm in the ACIM control reference?
3 visualizzazioni (ultimi 30 giorni)
Mostra commenti meno recenti
Hi Team,
I am studying vector control, so this may be a strange question.
I am looking to build an ACIM control reference in the architecture in the link below to implement vector control (FOC) of an AC induction motor.
URL: https://jp.mathworks.com/help/mcb/gs/implement-motor-speed-control-by-using-field-oriented-control-foc.html?s_tid=srchtitle_ site_search_1_%25E3%2583%2599%25E3%2582%25AF%25E3%2583%2588%25E3%2583%25AB%25E5%2588%25B6%25E5%25BE%25A1
Assuming that the feedback speed and reference speed (torque) are 0, the following simulation was performed to generate the reference current Iref.
Simulation Configuration
・ACIM control reference block (default value)
・Constant block (0)
・Scope

Iref = 0 in the forecast, but in the simulation it was about 0.24.

So my question is.
Why doesn't Iref_sd = 0 when I enter 0 for Tref and ωm in the ACIM control reference block with the parameters set to their default values?
Best regards
0 Commenti
Risposta accettata
Sam Chak
il 13 Feb 2025
Hi @中嶋
Your
and according to mathematical model of the AC Induction Motor (ACIM) Control Reference block, if the condition
is true, then the minimum function will be triggered. The block output is
.

0 Commenti