Simscape- Moist air error. Temperature at port B must be less than or equal to Maximum valid temperature.

52 visualizzazioni (ultimi 30 giorni)
</matlabcentral/answers/uploaded_files/139526/emosit_air_model.PNG> Attached image is my basic model, why am i getting assertion error.
An error occurred while running the simulation and the simulation was terminated Caused by: ['moist_air/Solver Configuration']: At time 134.033551, one or more assertions are triggered. See causes for specific information. Temperature at port B must be less than or equal to Maximum valid temperature. The assertion comes from: Block path: moist_air/Controlled Volumetric Flow Rate Source (MA).
Temperature at port A must be less than or equal to Maximum valid temperature. The assertion comes from: Block path: moist_air/Pipe (MA)1.
Please someone can help me with this?emosit_air_model.PNG

Risposte (2)

Martin
Martin il 22 Gen 2019
Hello Sachin,
One possibility is that the constant flow rate is causing a pressure rise in the Constant Volume Chamber. As the system keep trying to push the same flow into the chamber, the compression accompanies a rise in system temperature. Eventually this reaches the maximum setting for the network.
Try looking at the logged data to see if you see such a phenomenon happening.
Martin

SARA
SARA il 15 Feb 2023
Hello Sachin,
Could you please find a solution to this issue?
Thank you

Categorie

Scopri di più su Data Logging in Help Center e File Exchange

Prodotti

Community Treasure Hunt

Find the treasures in MATLAB Central and discover how the community can help you!

Start Hunting!

Translated by