Power factor regulation of Asynchronous Machine Block?

3 visualizzazioni (ultimi 30 giorni)
Hi,
When using the block asynchronous machine, where or how can I see the power factor of the system? In the parameters tab of the block I dont see anything. Is even possible to set this parameter? Or I just mus measure the active and reactive powers of the generator and calculate it?
Regards,

Risposte (1)

Sabin
Sabin il 26 Giu 2025
The power factor is not a plant parameter, can be adjusted using the control algorithm. We can compute the power factor based on measured power. To calculate the active and reactive power it is possible to use the built-in block Power Measurement (Three-Phase):

Categorie

Scopri di più su Specialized Power Systems in Help Center e File Exchange

Community Treasure Hunt

Find the treasures in MATLAB Central and discover how the community can help you!

Start Hunting!

Translated by