Power factor regulation of Asynchronous Machine Block?
3 visualizzazioni (ultimi 30 giorni)
Mostra commenti meno recenti
Hi,
When using the block asynchronous machine, where or how can I see the power factor of the system? In the parameters tab of the block I dont see anything. Is even possible to set this parameter? Or I just mus measure the active and reactive powers of the generator and calculate it?
Regards,
0 Commenti
Risposte (1)
Sabin
il 26 Giu 2025
The power factor is not a plant parameter, can be adjusted using the control algorithm. We can compute the power factor based on measured power. To calculate the active and reactive power it is possible to use the built-in block Power Measurement (Three-Phase):