PLC Coder does not support the usage of machine parented data. How can I solve it?

5 visualizzazioni (ultimi 30 giorni)
I am currently working on Stateflow (Simulink) to generate a PLC Code compatible with Rockwell.
I am currently facing incompatibility issue: PLC Coder does not support the usage of machine parented data objects. How can I solve it without deleting such data?
Thanks

Risposta accettata

Shivang
Shivang il 4 Set 2023
Hi Alice,
I understand you're running into an issue regarding the usage of machine-parented data objects in Stateflow.
Note that starting in R2023a, Stateflow charts no longer support machine-parented data. You will need to convert machine-parented data to chart-parented data store memory.
You can run Upgrade Advisor to fix this issue. Upgrade Advisor will automatically check the model for instances of machine-parented data. You will then be presented with an option to "Upgrade model", which will create chart-parented data in the charts that use machine-parented data.
Hope this helps.
-Shivang