issues on Heat exchanger in simscape 2P-TL
9 visualizzazioni (ultimi 30 giorni)
Mostra commenti meno recenti
My System-Level Condenser Evaporator (2P-TL) shows an error in my model.
Failed to determine size of heat exchanger from the specified nominal operating condition. Try reducing Nominal rate of heat transfer or increasing Try reducing Nominal rate of heat transfer or increasing Nominal mass flow rate.
There should be a problem with my heat exchanger cross-sectional area settings, but I can't fix it.
0 Commenti
Risposte (1)
runyi
il 12 Set 2024
1 Commento
Yifeng Tang
il 18 Set 2024
This error is saying that if the specified heat flow is honored, the outlet temperature of the hot fluid will be lower than the inlet temperature of the cold fluid, which violate the 2nd law of thermal dynamics. It's usually a parameterization error. Things to look for:
- Heat flow value and unit
- Fluid 1 flow rate, temperature and unit
- Fluid 2 flow rate, temperature and unit
- Fluid 1 & 2 fluid property block. Note each domain has different default working fluid.