Synchronous generator not responding correctly to loss of load

9 visualizzazioni (ultimi 30 giorni)
I’m doing a simple analysis of a synchronous machine running as a generator supplying a couple of loads. When power generated is greater than power demand there should be a frequency rise at the generator via the swing equation. However, doing multiple prebuilt simulations and tripping off load instead of rising frequency it’s always drops. I’ve adjusted inertia, governor valve settings, damping settings, time delay setting of governor.
  2 Commenti
Raghava S N
Raghava S N il 26 Nov 2024
Could you share the Simulink model you are working with?
Gordon Elgin
Gordon Elgin il 26 Nov 2024
Here's the simulink model I was working with. All it is a diesel generator and then a couple of resistive loads.

Accedi per commentare.

Risposte (1)

Gordon Elgin
Gordon Elgin il 26 Nov 2024
Spostato: Sabin il 10 Feb 2025
Just an update on my question. The reasoning for the error was within the breaker. Actually a signal of 0 actives the breaker and a signal of 1 deactivates the breaker. I was actually removing load instead of adding it.