Why the Three-Phase Breaker block in Simscape does not behavior as expected?

6 visualizzazioni (ultimi 30 giorni)
Dear all,
Let me introduce my problem. I am starting a model of a three-phase microgrid, but I am having some problems while usin the Three-Phase Breaker block since it doesn't behavior as expected: When I set the breaker to open state (Initial status - open / No switching any phase), I would expect that the voltage measured in the After Breaker scope were zero, but I am getting 20 kV instead. The same occurs when I set the breaker to close state. I would expect different voltage values depending on the breaker state.
Regarding the snubber parameters, Matlab's help says that Rs and Cs should be set to 0.1 and inf respectively when there is an inductor in series. Matlab also recommends to use the ode23tb solver for a most robust simulation. I am changing the snubber parameters to see if the system behavior changes, but it doesn't.
Did some of you have this problem before? Does someone know what could be the problem?
Thank you in advance for your help!
  1 Commento
habip yildirim
habip yildirim il 5 Feb 2023
I encountered such a problem and solved by switching powergui setting to "continuous" mode. It was "discrete" when I got error.

Accedi per commentare.

Risposte (2)

Mehran Mustafa
Mehran Mustafa il 24 Ott 2018
I'm having exactly the same problem. Did you find a solution to this yet?

Arjun Sujeeth
Arjun Sujeeth il 1 Nov 2021
Hey I would suggest this solution to you: try using 2 MOSFETS opposite to each other like shown in the Figure below. Thi should be a feasible solution