Azzera filtri
Azzera filtri

Info

Questa domanda è chiusa. Riaprila per modificarla o per rispondere.

How to tune PID for a Output(t) = k*Input(t) system?

1 visualizzazione (ultimi 30 giorni)
Richie
Richie il 10 Ago 2015
Chiuso: MATLAB Answer Bot il 20 Ago 2021
Hi,
Here comes a very simple system: Output(t) = k * Input(t), And a control reference of 1 is to be achieved.
I am adding a feedback PID controller to the system. I have two questions:
1. Is it correct to say that adding a PID controller with P is enough?
2. Is P = 1/k? Since if we make P = 1/k, in theory, the adjustment will be (-1/k*error), then the system will be perfectly compensated.

Risposte (1)

Arkadiy Turevskiy
Arkadiy Turevskiy il 13 Ago 2015
Plant model does not have an integrator in it, so you need an integral term to achieve zero steady-state error. In other words, if the controller is simply Kp, closed loop transfer function in Kp*K/(1+Kp*K). For Kp=1/K, closed loop transfer function is 1/K*K/(1+1/K*K)=1/2=0.5.
To get zero steady state error you need to add an intergral control. Integral control is all you really need in this case. Hope this helps.